Kategorie: e_hochtemperatur
High-temperature heat exchanger for textile industry
Reference example:
Heat recovery unit with rotary heat exchanger cassette type ICX-II-875 / D-X
Dimensions rotor cassette: L=1.850 x H=1.850 x D=500 mm
Space requirements heat recovery unit: L=2.600 x H=2.600 x D=2.000 mm
(rotor cassette, console, changeover molded parts, cleaning lance)
Performance data:
Heat transfer: 197kW
Efficiency: 75%
Exhaust air
Air amount: 14.000 mB³/h (operation)
10.179 m20³/h (related to 20°C)
Pressure loss: 87 Pa (related to 20°C)
Condition of air inlet temperature: 130°C
Condition of air outlet temperaure: 71°C
Supply air
Air amount: 9.131 mB³/h (operation
7.125 m20³/h (related to 20°C)
Pressure loss: 61 Pa
Condition of air inlet temperature: 20°C
Condition of air outlet temperature: 103°C