Kategorie: v_entfeuchtungsanlagen

RSX – Air dehumidification cassettes


RSX – air dehumidification cassettes are characterized by:

 

  • Solid welded construction
  • Drive with tooth-belt outside the airflow
  • Special circumferential sealing
  • Channel division sealings
  • Maintenance openings for drive motor in the dehumidifier cassette
  • Purge sector and bypass optional

 

Reference example: 
Air dehumidfication cassette type RSX 96/20
Dimensions of the rotor cassette: Width: 1.210 x height: 1.260 x depth: 285 mm

 

Performance data:


Process air
Process air amount (inlet): 6.000m3/h (at 20°C)
Process air temperature: 9°C
Process air humiditity, absolute: 7,2g/kg
Process air, relative: 100% rF

Process air amount (outlet): 6.000m3/h (at 20°C)
Process air temperature: 31°C +/-2°C
Process air humidity, absolute: ≤ 1,8g/kg

 

Regeneration air
Air amount (inlet): 2.200m3/h (at 20°C)
Air temperature (inlet): 32°C
Air humidity (inlet), absolute: 12g/kg
Air humidity (inlet), relative: 40%rF

Regeneration temperature: 120°C

Air amount (outlet): 2.200m3/h (bei 20°C)
Air temperature (outlet): 59°C +/-2°C
Air humidity (outlet), absolute: 28,1g/kg