Heat recovery for foil production


Reference example:
Heat recovery unit, incl. bypass, with roatry heat exchanger-cassette, type ICM-I-1400 / D-X
Dimensions rotor cassette: L=2.250 x H=2.250 x D=500 mm
Space requirements heat recovery unit including bypass: L=3.000 x H=4.000 x D=4.950 mm
(Rotor cassette, console, changeover molded parts, cleaning lance, damper bypass channels) 

 

Performance data:
Heat transfer: 713kW
Efficiency: 55%

 

Exhaust air

Air amount: 35.607 mB³H/h (operation)

                         20.126 Nm³/h

                         21.600 m20³/h (related to 20°C)

Pressure loss: 128 Pa (related to 20°C)

Condition of air inlet temperature: 210°C

Condition of air outlet temperature: 111°C

 

Supply air
Air amount: 29.609 mB³/h (operation)      
                         20.126 Nm³/h   
                         21.600 m20³/h (related to 20°C)
Pressure loss: 128 Pa (related to 20°C)
Condition of air inlet temperature: 30°C
Condition of air outlet temperature: 129°C