High-Temperature Heat Exchanger for the Textile Industry

Reference project
Heat exchangers for the textile industry comprise the following components:
- Choice between hot-dip galvanised, powder-coated and stainless steel welded construction
- Incl. duct connections (transition fittings) with maintenance openings
- Integrated automatic high-pressure cleaning with water and/or compressed air
- Various sealing variants / materials
- Duct partitioning optionally horizontal or vertical
- Integrated condensate tray
Design Example
Heat recovery system with rotary heat exchanger cassette: type ICX-II-875 / D-X
Rotor cassette dimensions: L=1,850 x H=1,850 x D=500 mm
Required installation space for heat recovery system: L=2,600 x H=2,600 x D=2,000 mm
Performance Data
Heat transfer: 197 kW, efficiency: 75 %
Exhaust air
Air volume 14,000 mB³/h, inlet temperature 130 °C, outlet 71 °C, pressure loss 87 Pa
Supply air
Air volume 9,131 mB³/h, inlet temperature 20 °C, outlet 103 °C, pressure loss 61 Pa