Application Example

Heat recovery system, including bypass, with rotary heat exchanger cassette: type ICM-I-1400 / D-X

Rotor cassette dimensions: L=2,250 x H=2,250 x D=500 mm

Required installation space for the heat recovery system: L=3,000 x H=4,000 x D=4,950 mm (rotor cassette, console, transition moulded parts, cleaning lance, louvre dampers, bypass ducts)

Performance Data

Heat transfer: 713 kW

Efficiency: 55 %

Exhaust Air

  • Air volume: 35,607 m³/h (operating) / 20,126 Nm³/h / 21,600 m³/h (referenced to 20 °C)
  • Pressure drop: 128 Pa (referenced to 20 °C)
  • Air inlet temperature: 210 °C
  • Air outlet temperature: 111 °C

Supply Air

  • Air volume: 29,609 m³/h (operating) / 20,126 Nm³/h / 21,600 m³/h (referenced to 20 °C)
  • Pressure drop: 128 Pa (referenced to 20 °C)
  • Air inlet temperature: 30 °C
  • Air outlet temperature: 129 °C